Loading...
B-16 ALPS Advanced Line Protection System
GE Power Management
B.2 REGISTER MAPS APPENDIX B
B
F10 16 bits SYS_MISCSTAT1
bit 0 Protection disabled fla
g
bit 1 N/A
bit 2 Continuous monitor alarm error
bit 3 Unbalanced system detection error
bit 4 Fuse failure error
bit 5 Trip bus check error
bits 6 to 11 N/A
bit 12 Time strobe fail (to be looked into)
bit 13 Jumper (remote manual trip/close)
bit 14 Jumper (Remote chan
g
e settin
g
s/
Soft DO enable/disable)
bit 15 Jumper (keypad enabled/disabled)
F11 16 bits SYS_MISCSTAT2 (16 bits)
bit 0 Group selection throu
g
h contact
converters
bit 1 Relay test
bit 2 Di
g
ital output test
bit 3 Channel test
bit 4 Playback
bit 5 MMI passwords enabled/disabled
bit 6 Lo
g
on failure throu
g
h front port
bit 7 Lo
g
on failure throu
g
h Rear port#1
bit 8 Lo
g
on failure throu
g
h Rear port#2
bit 9 D.O. software disable fla
g
bit 10 Comm. access level - low bit
bit 11 Comm. access level - hi
g
h bit
bit 12 Factory Settin
g
access level
bit 13 Active settin
g
g
roup - low bit
bit 14 Active settin
g
g
roup - hi
g
h bit
bit 15 N/A
F12 Integer Comm Port 1 Settings (xxyz)
F56 Baud Rate (xx)
F57 Parity (y)
F58 Stop Bits (z)
F13 Integer Comm Port 2 Settings (ixxyz)
F59 Interface (i)
F56 Baud Rate (xx)
F57 Parity (y)
F58 Stop Bits (z)
F14 2 bytes Fault Data
F18 Fault Type (Lower byte)
F17 Trip Type (Upper byte)
Table B–5: DATA FORMATS (Sheet 3 of 12)
TYPE VALUE/
BITMASK
DESCRIPTION
F17 2 bytes Trip Types
0 No trip available
1Z1
2Z2
3Z3
4Z4
5PLT
6 50G
7 50P
8 51G
9LPU
10 REM
11 WI
12 OSC
13 SZ1
14 SZ2
15 SP1
16 SWI
17 CTB
255 Undefined
F18 2 bytes Fault Types
1 AG_-phase A to Ground
2 BG_-phase B to Ground
3 CG_-phase C to Ground
4 ABG-phase A to phase B to Ground
5 BCG-phase B to phase C to Ground
6 CAG-phase C to phase A to Ground
7 AB_-phase A to phase B
8 BC_-phase B to phase C
9 CA_-phase C to phase A
10 3PH-phase A to phase B to phase C
255 Undefined
F20 2 bytes Download Status
0OK
1 Erasin
g
Flash RAM
2 Communication Error
3 Code CRC Error
4 Flash Write Error
5 Flash Erase Error
6 Incorrect Application Error
7 Incorrect Size
8 Computin
g
application code CRC
Table B–5: DATA FORMATS (Sheet 4 of 12)
TYPE VALUE/
BITMASK
DESCRIPTION

Table of Contents