EasyManua.ls Logo

GE ALPS - Page 123

GE ALPS
366 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GE Power Management
ALPS Advanced Line Protection System 2-59
2 CALCULATION OF SETTINGS 2.5 REFERENCE TABLES
2
613 51GPCKUPFF 51G Pickup durin
g
fuse failure 0.20 to 15.0 amps
step 0.01
0.04 to 3.0 amps
step 0.01
2.0 A at 5A
0.4 A at 1A
614 51GCURVE 51G Curve INV, V-INV, E-INV, CUSTOM, DEFT V-INV
615 51GTIMDIAL 51G Time Dial 0.5 to 10.0 step 0.1 5
616 DEFTIMDELY Definite Time Delay 0.5 to 30.0 sec. step 0.1 1.0 sec.
617 51G_RESET 51G Reset Characteristic FAST, EM FAST
VOLTAGE
701 RATEDVOLTS Rated Per Unit Volta
g
e 100, 105,110,115, 120 volts 115 volts
702 PHASEOVER Select Phase Overvolta
g
eNO, YES NO
703 PHOVPICKUP Phase Overvolta
g
e Pickup 0.0 to 1.4 p.u. volts step 0.01 1.4 V
704 PHOVTMDLY Phase Overvolta
g
e Time Delay 0.0 to 10.0 sec. step 0.01 0.50 sec.
705 V1OVER Select Positive Sequence
Overvolta
g
e (Overvolta
g
e Model
Only)
NO, YES NO
706 V1OVINSTPU Instantaneous Positive Sequence
Overvolta
g
e Pickup (Overvolta
g
e
Model Only)
1.0 to 1.4 p.u. volts step 0.01 1.25 p.u. V
707 V1OVTIMPU TOV Positive Sequence
Overvolta
g
e Pickup (Overvolta
g
e
Model Only)
1.0 to 1.4 p.u. volts step 0.01 1.25 p.u. V
708 V1OVTIMDLY Positive Sequence Overvolta
g
e
Time Delay (Overvolta
g
e Model
Only)
0.0 to 10.0 sec. step 0.01 sec. 0.25 sec.
709 V1COMP Compensated Positive Sequence
Overvolta
g
e (Overvolta
g
e Model
Only)
NO, YES NO
710 V1COMPRCH Compensated Positive Sequence
Overvolta
g
e Impedance
(Overvolta
g
e Model Only)
0.01 to 50.0 ohms
step 0.01
0.05 to 250.0 ohms
step 0.05
6.0 at 5A
30.0 at 1A
711 V1COMPINPU INST Compensated Positive
Sequence OV Pickup
(Overvolta
g
e Model Only)
0.0 to 1.4 p.u. volts step 0.01 1.4 p.u. V
712 V1COMPTDPU TOV Compensated Positive
Sequence OV Pickup
(Overvolta
g
e Model Only)
0.0 to 1.4 p.u. volts step 0.01 1.4 p.u. V
713 V1COMPTDLY Compensated Positive Sequence
OV Time Delay (Overvolta
g
e
Model Only)
0.0 to 10.0 sec. step 0.01 0.3 s at 5A
1.5 s at 1A
714 FUSEFAIL Potential Fuse Failure Blockin
g
NO, YES YES
BLK RECLOS
801 ALL_BELOW Block reclosin
g
for any function NO, YES NO
802 OUTOFSTEP Block for Out of Step NO, YES NO
803 ALL_3_Z2PH Block for 3 phase faults NO, YES NO
804 50G_BLOCK Block for 50G trip NO, YES NO
805 Z2TIMETRIP Block for Z2 Time Delayed Trip NO, YES NO
806 Z3TIMETRIP Block for Z3 Time Delayed Trip NO, YES NO
807 Z4TIMETRIP Block for Z4 Time Delayed Trip NO, YES NO
808 Z1PHASTRIP Block for any Z1 Phase Fault NO, YES NO
809 ANYZ2PHASE Block for any Z2 Phase Fault NO, YES NO
810 CONFGTRIP Block For Confi
g
urable Trip Lo
g
ic NO, YES NO
LINEPICKUP
901 LINEPICKUP Select Line Pickup NO, YES NO
Table 2–11: PROTECTION SETTINGS GUIDE (Sheet 3 of 7)
NO. MNEMONIC DESCRIPTION RANGE (5A) RANGE (1A) DEFAULT
Settin
g
value QUAD applies to Revision B models only.
Settin
g
applicable to Revision B models only.
^
Settin
g
applicable to Sin
g
le Phase Trippin
g
models only.

Table of Contents

Related product manuals