3041 EXPONENT R/W P10 1 10 to 20 - 20
3042 MAX_OP R/W Inte
er 1 0 to 9999 - 0
3043 MAX_IXT R/W F48 1 A
x
sec. 0
3044 IXTPHASEA R/W F48 1 A
x
sec. 0
3045 IXTPHASEB R/W F48 1 A
x
sec. 0
3046 IXTPHASEC R/W F48 1 A
x
sec. 0
3047 NUM_OP R/W Inte
er 1 0 to 9999 - 0
3048 NUM_OP_A R/W Inte
er 1 0 to 9999 - 0
3049 NUM_OP_B R/W Inte
er 1 0 to 9999 - 0
3050 NUM_OP_C R/W Inte
er 1 0 to 9999 - 0
GENERAL SETTINGS: INPUTS
3051 CC1 R/W Inte
er 1 0 to 32 - 12
3052 CC2 R/W Inte
er 1 0 to 32 - 13
3053 CC3 R/W Inte
er 1 0 to 32 - 10
3054 CC4 R/W Inte
er 1 0 to 32 - 11
3055 CC5 R/W Inte
er 1 0 to 32 - 7
3056 CC6 R/W Inte
er 1 0 to 32 - 0
3057 CC7 R/W Inte
er 1 0 to 32 - 1
3058 CC8 R/W Inte
er 1 0 to 32 - 2 (1-phase)
4 (3-phase)
3059 CC9 R/W Inte
er 1 0 to 32 - 3
3060 CC10 R/W Inte
er 1 0 to 32 - 4
3061 CC11 R/W Inte
er 1 0 to 32 - 5
3062 CC12 R/W Inte
er 1 0 to 32 - 6
3063 Reserved RO - - - - - - -
↓↓ RO - - - - - - -
3099 Reserved RO - - - - - - -
GENERAL SETTINGS: MISCELLANEOUS
3100 Group Settin
R/W 1 1 to 4 - - -
3101 Reset Type WO F43 1 0 to 4 - - -
3102 Reserved - - - - - - - -
↓↓ -- - - - ---
3108 Reserved - - - - - - - -
3109 Station ID R/W ASCII 16 - - - - -
3125 Line ID R/W ASCII 16 - - - - -
3141 Reserved RO - - - - - - -
↓↓ RO - - - - - - -
3199 Reserved RO - - - - - - -
PROTECTION SETTINGS: ZONE 1 DISTANCE
3200 Z1PHASE R/W Inte
er 1 0 = No, 1 = Yes - 1
3201 Z1PHREACH R/W P100 1 5 to 25000 1 to 5000 Ω 2700 540
3202 Z1PLEVDET R/W P10 1 0 to 99 pu V 0
3203 Z1GROUND R/W Unsi
ned Int 1 0 = No, 1 = Yes - 1
3204 Z1GRDREACH R/W P100 1 5 to 25000 1 to 5000 Ω 2700 540
3205 Z1GRDCHAR R/W Unsi
ned Int 1 0=Mho, 1=React - 0
3206 Z1SUREACH R/W P100 1 5 to 25000 1 to 5000 Ω 10000 2000
Table B–4: MODBUS MEMORY MAP (Sheet 4 of 10)
ALPS
REGISTER
CONTENTS TYPE FORMAT NO. OF
REGS.
RANGE UNITS DEFAULT
1A 5A 1A 5A
1, 2, 3, 4, 5, 6, 7, 8
See pa