EasyManua.ls Logo

GE ALPS - Page 43

GE ALPS
366 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GE Power Management
ALPS Advanced Line Protection System 1-31
1 PRODUCT DESCRIPTION 1.8 PROTECTION SCHEMES
1
In a typical application with ON-OFF carrier sets, only one receiver is used at each terminal of the line, regardless of the
number of line terminals. The contact converter (RCVR 1 in the logic diagram) converts the receiver output into a blocking
signal usable by the ALPS. Some blocking schemes use frequency-shift tone channels, such as the GE type NS40A. For a
three-terminal application employing FSK tones, each terminal has two receivers and an additional contact converter must
be assigned. In the default settings, CC2 is used.
Figure 1–15: BLOCKING SCHEME LOGIC DIAGRAM
External contacts may be used to supervise the relay-channel interface. The EXTERNAL STOP CARRIER signal is
assigned to CC3 in the default settings. EXTERNAL STOP CARRIER turns the local transmitter OFF. This feature is typi-
cally used when the remote breaker must trip to clear a fault following a breaker failure. An external contact closure, indicat-
ing a breaker failure, produces an output from CC3 that turns the transmitter OFF, permitting the remote end to trip.
FAULT
DETECTOR
LINE PICKUP
(CANCL)
(RI)
3
4
F=1-50
TL1
F
50
25
X
B
0
3
407
3
8
301
508
302
209
22
213
208
CARRIER
START
CARRIER
STOP
OSB
(Zone 2)
TL24
2
[2 RCVRS]
[1 RCVR]
21
CC
(RCVR1)
CC
(RCVR2)
TL2G
B
0
REF
REF
B = 0.2- 3.0 SEC
CC
(STCR)
PHASE
DISTANCE
GROUND
DISTANCE
GROUND
DIRECTIONAL
OVER-
CURRENT
TRIP
BLOCK
REMOTE
OPEN
PHASE
DISTANCE
GROUND
DISTANCE
110
GROUND
BACKUP
OVER-
CURRENT
SUPERVISION
PHASE
DISTANCE
GROUND
DISTANCE
PHASE
DISTANCE
GROUND
DISTANCE
PHASE
BACKUP
50P
P
X
TL25
X=30-300
OSBALL
FFB
Setting 714
C
0
C
0
D
0
D
0
TL4G
TL4P
TL3G
TL3P
13
503
20
28
12
BLOCK ZONE 1
Setting 110
1
103
2
25
11
C=0.4-6sec
D=0.4-6sec
(Zone 4)
(Zone 3)
TIME DELAYED TRIP
REVERSIBLE
ZONE 4
ZONE 3
ZONE 1
OVERREACHING ZONE /
ZONE 2
13
Setting
1202
EXTERNAL
CARRIER STOP
EXTERNAL
BLOCK PILOT
TRIPPING
(KEY1)
(KEY2)
Setting
205
BlockScheme.vsd
OUT OF STEP
BLOCKING
LOGIC
OSB
Settings
1601 - 1607
(CNFTRP)
CONFIGURABLE
TRIP BUS
8
RECLOSE CANCEL
RECLOSE INITIATE
BLOCK RELCLOSING
Settings 801-810
9
(TRIP)
TRIP
BUS
44
7
7
6
303
103
BLOCK ZONE 1
Setting 110
Supervise Zone 4
FFB
Setting 714
PT FUSE
FAILURE
DETECTION
LOGIC
FFB
Setting 714
BLOCKS SELECTED PHASE AND
GROUND ZONE FUNCTIONS
DURING OUT OF STEP
CONDITION
X=30-300
T2LP
CC
(STCR)
51G
50G
IT
IB
9

Table of Contents

Related product manuals