5-26 L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP CHAPTER 5: SETTINGS
5
Pushbuttons (both user-control buttons and user-programmable buttons) located on the front panel can be pressed by an
Administrator or Engineer role. This also applies to the
RESET button, which resets targets, where targets are errors
displayed on the front panel or the Targets panel of the EnerVista software. The RESET button has special behavior in that it
allows these two roles to press it even when they are logged in through the RS232 port and not through the front panel.
To reset the security event log and self-test operands:
1. Log in as Supervisor (if the role is enabled) or Administrator (if the Supervisor role is disabled) and execute a clear
security command under Commands > Security > Clear Security.
Security events
The security events produced when the CyberSentry option is purchased are sent as sytem log (syslog) messages to a
syslog server, if one is configured. The format is as follows.
Event Number — Event identification number (index)
Date & Timestamp — UTC date and time
Username — 255 chars maximum, but in the security log it is truncated to 20 characters
IP address — Device IP address
Role — 16 bit unsigned, of type format F617
Activity Value — 16 bit unsigned
If "System Integrity Recovery" events are logged during a restart of the unit due to an incorrect shutdown sequence,
upgrade the firmware to version 7.31 or later to correct this issue.
Security log Event Number Date &
Timestamp
Username IP address Role Activity Value
Enumeration Role
0None
1 Administrator
2Supervisor
3Engineer
4Operator
5Factory
Enumeration Description
1 Authentication Failed
2User Lockout
3 FW Upgrade
4FW Lock
5 Settings Lock
6 Settings Change. Because this can fill the entire event log, it is supported by the
already existing Settings_Change.log file. This event is not required.
7 Clear Oscillography command
8 Clear Data Logger command (not applicable to all UR products)
9 Clear Demand Records command (not applicable to all UR products)
10 Clear Energy command (not applicable to all UR products)
11 Clear Unauthorized Access command
12 Clear Teleprotection Counters command (not applicable to all UR products)
13 Clear All Relay Records command
14 Role Log in
15 Role Log off

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE L90 and is the answer not in the manual?

GE L90 Specifications

General IconGeneral
CommunicationEthernet, Serial
MountingPanel Mount
Frequency50/60 Hz
InputsDigital, Analog
OutputsRelay
ControlLocal, Remote
Communication InterfaceIEC 61850, DNP3, Modbus
Protection FunctionsDifferential, Ground Fault
Standards ComplianceIEC, IEEE