5-222 L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
GROUPED ELEMENTS CHAPTER 5: SETTINGS
5
Figure 5-110: Stub bus logic
5.7.4 Line pickup
SETTINGS  GROUPED ELEMENTS SETTING GROUP 1(6)  LINE PICKUP
LINE PICKUP
LINE PICKUP
FUNCTION: Disabled
Range: Disabled, Enabled
LINE PICKUP SIGNAL
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
PHASE IOC LINE
PICKUP: 1.000 pu
Range: 0.020 to 30.000 pu in steps of 0.001
LINE PICKUP UV PKP:
0.700 pu
Range: 0.004 to 3.000 pu in steps of 0.001
LINE END OPEN PICKUP
DELAY: 0.150 s
Range: 0.000 to 65.535 s in steps of 0.001
LINE END OPEN RESET
DELAY: 0.090 s
Range: 0.000 to 65.535 s in steps of 0.001
LINE PICKUP OV PKP
DELAY: 0.040 s
Range: 0.000 to 65.535 s in steps of 0.001
AR CO-ORD BYPASS:
Enabled
Range: Disabled, Enabled
AR CO-ORD PICKUP
DELAY: 0.045 s
Range: 0.000 to 65.535 s in steps of 0.001
AR CO-ORD RESET
DELAY: 0.005 s
Range: 0.000 to 65.535 s in steps of 0.001
TERMINAL OPEN:
Off
Range: FlexLogic operand
AR ACCELERATE:
Off
Range: FlexLogic operand
LINE PICKUP DISTANCE
TRIP: Enabled
Range: Disabled, Enabled
LINE PICKUP BLOCK:
Off
Range: FlexLogic operand
LINE PICKUP
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
LINE PICKUP
EVENTS: Disabled
Range: Disabled, Enabled