EasyManua.ls Logo

GE L90

GE L90
900 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5-142 L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
SYSTEM SETUP CHAPTER 5: SETTINGS
5
Figure 5-63: Example of use of sources
5.5.4 87L power system
5.5.4.1 Menu
SETTINGS  SYSTEM SETUP  87L POWER SYSTEM
Y LV D HV AUX
SRC 1 SRC 2 SRC 3
Phase CT M1 F1+F5 None
Ground CT M1 None None
Phase VT M5 None None
Aux VT None None U1
87L POWER SYSTEM
NUMBER OF TERMINALS:
2
Range: 2, 3
NUMBER OF CHANNELS:
1
Range: 1, 2
CHARGING CURRENT
COMPENSATN: Disabled
Range: Disabled, Enabled
POS SEQ CAPACITIVE
REACTANCE: 0.100 k
Range: 0.100 to 65.535 kin steps of 0.001

Table of Contents

Related product manuals