5-150 L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
SYSTEM SETUP CHAPTER 5: SETTINGS
5
5.5.5 Breakers
SETTINGS  SYSTEM SETUP  BREAKERS BREAKER 1(4)
BREAKER 1
BREAKER 1
FUNCTION: Disabled
Range: Disabled, Enabled
BREAKER1 PUSH BUTTON
CONTROL: Disabled
Range: Disabled, Enabled
BREAKER 1 TAGGING:
Disabled
Range: Disabled, Enabled
BREAKER 1
SUBSTITUTN: Disabled
Range: Disabled, Enabled
BREAKER 1 BYPASS:
Disabled
Range: Disabled, Enabled
BREAKER 1 AR BLOCK:
Disabled
Range: Disabled, Enabled
BREAKER 1 NAME:
Bkr 1
Range: up to six alphanumeric characters
BREAKER 1 MODE:
3-Pole
Range: 3-Pole, 1-Pole
BREAKER 1 OPEN:
Off
Range: FlexLogic operand
BREAKER 1 BLK OPEN:
Off
Range: FlexLogic operand
BREAKER 1 CLOSE:
Off
Range: FlexLogic operand
BREAKER 1 BLK CLOSE:
Off
Range: FlexLogic operand
BREAKER1 ΦA/3P CLSD:
Off
Range: FlexLogic operand
BREAKER1 ΦA/3P OPND:
Off
Range: FlexLogic operand
BREAKER 1 ΦB CLOSED:
Off
Range: FlexLogic operand
BREAKER 1 ΦB OPENED:
Off
Range: FlexLogic operand
BREAKER 1 ΦC CLOSED:
Off
Range: FlexLogic operand
BREAKER 1 ΦC OPENED:
Off
Range: FlexLogic operand
BREAKER 1 TOPERATE:
70 ms
Range: 0 to 65535 s in steps of 1
BREAKER 1 EXT ALARM:
Off
Range: FlexLogic operand
BREAKER 1 ALARM
DELAY: 0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
MANUAL CLOSE RECAL1
TIME: 0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
BREAKER 1 OPEN
SEAL-IN: 0.000 s
Range: 0.000 to 65.535 s in steps of 0.001