EasyManua.ls Logo

GE L90

GE L90
900 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHAPTER 5: SETTINGS SYSTEM SETUP
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-141
5
Figure 5-62: Disturbance detector logic
The disturbance detector responds to the change in currents of twice the current cut-off level. The default cut-off threshold
is 0.02 pu; thus by default the disturbance detector responds to a change of 0.04 pu. The metering sensitivity setting
(
PRODUCT SETUP  DISPLAY PROPERTIES  CURRENT CUT-OFF LEVEL) controls the sensitivity of the disturbance detector
accordingly.
5.5.3.4 Example for use of sources
An example of the use of sources is shown in the following figure. A relay can have the following hardware configuration:
This configuration can be used on a two-winding transformer, with one winding connected into a breaker-and-a-half
system. The following figure shows the arrangement of sources used to provide the functions required in this application,
and the CT/VT inputs that are used to provide the data.
Increasing slot position letter -->
UR CT/VT module 1 CT/VT module 2 CT/VT module 3
B30, B90, C70, F35, N60, T35 8 CTs 4 CTs, 4 VTs 4 CTs, 4 VTs
C60, D60, G30, G60, L30, L90, M60, T60 CTs VTs not applicable

Table of Contents

Related product manuals