EasyManuals Logo

GE L90 User Manual

GE L90
900 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #441 background imageLoading...
Page #441 background image
CHAPTER 5: SETTINGS GROUPED ELEMENTS
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-217
5
5.7.3 Line differential elements
SETTINGS  GROUPED ELEMENTS SETTING GROUP 1(6) LINE DIFFERENTIAL ELEMENTS
5.7.3.1 Current differential (ANSI 87L)
SETTINGS  GROUPED ELEMENTS SETTING GROUP 1(6) LINE DIFFERENTIAL... CURRENT DIFFERENTIAL
LINE DIFFERENTIAL
ELEMENTS
CURRENT
DIFFERENTIAL
See below
STUB BUS
See page 5-221
CURRENT
DIFFERENTIAL
CURRENT DIFF
FUNCTION: Disabled
Range: Disabled, Enabled
CURRENT DIFF SIGNAL
SOURCE 1: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
CURRENT DIFF SIGNAL
SOURCE 2: None
Range: None, SRC 1, SRC 2, SRC 3, SRC 4
CURRENT DIFF SIGNAL
SOURCE 3: None
Range: None, SRC 1, SRC 2, SRC 3, SRC 4
CURRENT DIFF SIGNAL
SOURCE 4: None
Range: None, SRC 1, SRC 2, SRC 3, SRC 4
CURRENT DIFF BLOCK:
Off
Range: FlexLogic operand
CURRENT DIFF
PICKUP: 0.20 pu
Range: 0.10 to 4.00 pu in steps of 0.01
CURRENT DIFF
CT TAP 1: 1.00
Range: 0.20 to 5.00 in steps of 0.01
CURRENT DIFF
CT TAP 2: 1.00
Range: 0.20 to 5.00 in steps of 0.01
CURRENT DIFF
RESTRAINT 1: 30%
Range: 1 to 50% in steps of 1
CURRENT DIFF
RESTRAINT 2: 50%
Range: 1 to 70% in steps of 1
CURRENT DIFF
BREAK PT: 1.0 pu
Range: 0.0 to 20.0 pu in steps of 0.1
INRUSH INHIBIT MODE:
Disabled
Range: Disabled, Per phase, 2-out-of-3, Average
INRUSH INHIBIT
LEVEL: 20% fo
Range: 1.0 to 40.0% f
0
in steps of 0.1
CURRENT DIFF GND
FUNCTION: Disabled
Range: Disabled, Enabled
CURRENT DIFF GND
PICKUP: 0.10 pu
Range: 0.05 to 1.00 pu in steps of 0.01
CURRENT DIFF GND
RESTRAINT: 25%
Range: 1 to 50% in steps of 1
CURRENT DIFF GND
DELAY: 0.10 s
Range: 0.00 to 5.00 s in steps of 0.01
CURRENT DIFF DTT:
Enabled
Range: Disabled, Enabled

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE L90 and is the answer not in the manual?

GE L90 Specifications

General IconGeneral
CommunicationEthernet, Serial
MountingPanel Mount
Frequency50/60 Hz
InputsDigital, Analog
OutputsRelay
ControlLocal, Remote
Communication InterfaceIEC 61850, DNP3, Modbus
Protection FunctionsDifferential, Ground Fault
Standards ComplianceIEC, IEEE

Related product manuals