EasyManua.ls Logo

GE L90

GE L90
900 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHAPTER 10: THEORY OF OPERATION DISTANCE ELEMENTS
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 10-25
10
Phase distance fault type supervision can be enabled/disabled through SETTINGS  GROUPED ELEMENTS SETTING
GROUP 1(6)  DISTANCE  PH DIST PH SELECT SUPV
and is applied to phase distance zone 1 to zone 3 only. G60 and L60
relays do not employ fault type supervision for the phase distance in all zones.
10.3.3.11 Zero-sequence directional characteristic
The extra zero-sequence characteristic applies to ground zones 2 and higher and is achieved by checking angles between:
A ground element — I_0 × Z
D
and –V_0
B ground element — I_0 × Z
D
and –V_0
C ground element — I_0 × Z
D
and –V_0
The limit angle of the comparator is not adjustable and equals 90°. The zero-sequence directional characteristic improves
directional integrity for time-delayed operations after the memory expires.
10.3.3.12 Overcurrent supervision
The overcurrent supervision responds to the following currents:
AB phase element — (I
A
– I
B
) /
BC phase element — (I
B
– I
C
) /
CA phase element — (I
C
– I
A
) /
A, B, C ground element — | 3 × I_0 – 0.05 × I_1 |
The following tables summarize the characteristics of the distance elements.
Table 10-1: Directional mho phase distance functions
Table 10-2: Directional mho ground distance functions
Table 10-3: Directional quadrilateral phase distance functions
Characteristic Comparator inputs Limit angle
Variable mho I × Z – V V_1M COMP LIMIT
Reactance I × Z – V I × ZCOMP LIMIT
Directional I × ZD V_1M DIR COMP LIMIT
Fault type NOT SLG See the Fault Type Characteristic section Removed during open pole conditions
Characteristic Comparator inputs Limit angle
Variable mho I × Z – V V_1M COMP LIMIT
Reactance I × Z – V I_0 × ZCOMP LIMIT
Directional I_0 × Z
D
V_1M DIR COMP LIMIT
Directional I_2 × Z
D
V_1M DIR COMP LIMIT (removed when 3I_0 > OC SUPV and I_2 < CUTOFF)
Fault-type I_0 I_2 50° (removed during open pole conditions or when 3I_0 > OC SUPV
and I_2 < CUTOFF)
Zero-sequence I_0 × Z
D
–V_0 90° (zones 2 and higher only; removed for zones 2 and higher
during open pole conditions)
Characteristic Comparator inputs Limit angle
Reactance I × Z – V I × ZCOMP LIMIT
Directional I × Z
D
V_1M DIR COMP LIMIT
Right Blinder I × Z
R
– V I × Z
R
90°
Left Blinder I × Z
L
– V I × Z
L
90°
Fault type NOT SLG See the Fault Type Characteristic section Removed during open pole conditions

Table of Contents

Related product manuals