2-20 MIB High Impedance Bus Differntial Relay GEK-106426B
2.10 TECHNICAL SPECIFICATIONS. 2 PRODUCT DESCRIPTION
2
Max. Ratings for 100.000 operations:
2.10.6 COMMUNICATIONS
2.10.7 ENVIRONMENTAL
VOLTAGE
MAKE&CARRY
CONTINUOUS
MAKE&CARRY 0.2 SEC BREAK MAX LOAD
DC Resistive
24 Vdc 16 A 48 A 16 A 384W
48 Vdc 16 A 48 A 2.6 A 125W
125 Vdc 16 A 48 A 0.6 A 75 W
250 Vdc 16 A 48 A 0.5 A 125 W
AC Resistive
120 Vac 16 A 48 A 16 A 1920 VA
250 Vac 16 A 48 A 16 A 4000 VA
AC Inductive
PF = 0.4
250 Vac 10 A 30 A 10 A 1000 VA
FRONT PORT RS232 300, 600, 1200, 2400, 4800, 9600 or 19200 bps,
Modbus® RTU
REAR PORT RS485 300, 600, 1200, 2400, 4800, 9600 or 19200 bps,
Modbus® RTU
Operating Temperatures: -20º C to +60º C
Ambient Storage Temperatures: -40º C to +80º C
Maximum relative humidity 95%
Altitude 2000 m. Max
Pollution Degree 2