GEK-106426B MIB High Impedance Bus Differntial Relay 2-23
2 PRODUCT DESCRIPTION 2.11 TECHNICAL SPECIFICATIONS FOR HID MODULE
2
2.11.5 PRODUCTION TESTS
2.11.6 APPROVALS
Manufactured under an ISO9001 Registered system
CE Marking
Electrostatic Discharge: IEC 60255-22-2
EN 61000-4-2
IV
8 kV in contact,
15 kV through air.
Radiointerference: IEC 60255-22-3: 40 MHz, 151 MHz, 450
MHz and cellular phone.
III
Radiated Electromagnetic fields with
amplitude modulation.
ENV 50140 10 V/m
Radiated Electromagnetic fields with
amplitude modulation. Common mode.
ENV 50141 10 V/m
Radiated Electromagnetic fields with
frequency modulation.
ENV 50204 10 V/m
Fast Transients: ANSI/IEEE C37.90.1
IEC 60255-22-4
BS EN 61000-4-4
IV
IV
IV
Magnetic fields at industrial frequency: EN 61000-4-8 30 AV/m
Power Supply interruptions: IEC 60255-11
Temperature: IEC 57 (CO) 22
RF Emission: EN 55011 B
Sinusoidal Vibration: IEC 60255-21-1 II
Shock: IEC 60255-21-2 I
Insulation Test: IEC255-5 (Tested on CTs, Power Supply terminals, Contact
Inputs and Contact Outputs)