V 09/18
30 • Start-up and operation OptiStar CG06 Automatic gun control unit
Pin Bit Function (binary value)
L 11 IN-A2 Identification number binary value 2
2
(=4)
M 12 IN System ON/OFF (gun release)
N 13 IN Strobe (data transfer from data Bus)
O 14 IN Remote/manual
P 15 IN Preset values program no. binary value 2^8 (=256) reserve
R 16 IN GND external
S 1 OUT Composite error message (signal: Error)
T 2 OUT System activated
U 24 VDC external
Enclosure Shield
Initial start-up
Setting the device type
Adjust the corresponding device type (manual device types or automatic
device) with the system parameter P0 (see therefore in chapter "System
parameters").
NOTE:
If the control unit is supplied as a component of an OptiFlex auto-
matic unit, then the corresponding system parameter is set correct-
ly by the factory!
System parameter P0=3
Preparing the powder hopper/container
Prepare the powder hopper or powder box (reference the corresponding
operating manual).
Switch on the booth
Switch on the powder coating booth according to its operating manual.
Daily start up
The daily start-up of the OptiStar CG06 Automatic gun control unit takes
place by the following steps:
Select the operating mode
Select the application mode with three predefined modes (Preset mode)
or the user-defined program mode with 250 adjustable programs (Pro-
gram mode).
1. Turn on the gun control unit with the ON key
2. Select the corresponding application mode with key T12 (for
Program mode) or keys T13/T14/T15 (for Preset mode)