117
Secti
on
OEM
POWERTRONIX
MIZAR
Adres
se
Name
ALCOR
QUASAR
SUPERNOVAE
100
Outpower Phase 1 %
x
x
x
101
Outpower Phase 2 %
x
x
x
102
Outpower Phase 3 %
x
x
x
103
Battery Capacity %
x
x
x
104
Input Voltage Phase 1 V
x
x
x
105
Input Voltage Phase 2 V
x
x
x
106
Input Voltage Phase 3 V
x
x
x
107
Temperature °C
not supported
x
x
108
Autonomy Time minutes
x
x
x
109
UPS Status (ASCII Hex)
x
x
x
110
Battery Voltage V
x
x
x
111
Input Frequency Phase 1 Hz
not supported
x
not supported
112
Input Frequency Phase 2 Hz
not supported
x
not supported
113
Input Frequency Phase 3 Hz
not supported
x
not supported
114
Powerfail Counter
x
x
x
115
Alarm: Battery Bad
x
x
x
116
Alarm: On Battery
x
x
x
117
Alarm: Battery Low
not supported
not
supported
x
118
Alarm: Battery Depleted
x
not
supported
x
119
Alarm: Overtemperature
x
not
supported
x
120
Alarm: Input Bad
x
x
x
121
Alarm: Output Bad
not supported
x
not supported
122
Alarm: Output Overload
x
x
x
123
Alarm: On Bypass
x
x
x
124
Alarm: Bypass Bad
x
x
x
125
Alarm: Output Off As
Requested
x
x
x
126
Alarm: UPS Off As Requested
x
x
x
127
Alarm: Charger Failed
x
x

Table of Contents