CA.pl –sign
Now create an empty file named “rccmd.pem“ and copy the cert information of newcert.pem
(rccmd certificate), newkey.pem (private key) and cacert.pem (CA) into it. Please note, that the
exact copying is required to use it without trouble!
Use your own RCCMD certificate
Do the following steps at the RCCMD Client and every sender (e. g. UPS Web Manager):
Backup the existing “rccmd.pem”
Replace the existing “rccmd.pem” with your own
Restart the RCCMD Client
Restart the RCCMD Sender
RCCMD client as relay station)
Note: The RCCMD timeout is 60 seconds, meaning that after this time the
communication to the RCCMD client will be stopped and a logfile entry
will be made. When an OK response from the client is received, the
system assumes a successful RCCMD Shutdown and proceeds with a
shutdown of the next 50 RCCMD clients. Every minute one batch of up
to 50 RCCMD clients can be executed without SSL.
License regulations:
Please note that in order to use these functions legally, the corresponding RCCMD client
program is installed and started from the UPS-Management Software CD. The RCCMD
license code can only be used once per installation. If more computers need to be added to