68
796688 (4188-657)_i2 _06/03
Any service and maintenance work on the panel or system must be carried out by a
trained maintenance engineer from the fire alarm servicing organisation.
Message displayed Description and checks
Panel earth fault
There is an earth fault at the panel.
Check the earth connections to the panel.
Panel in customer
mode
The panel is now in customer mode that is at access level 3.
Panel in
engineering mode
The panel is now in engineering mode, that is at access
level 4.
Panel in fire -
Access denied
Access to the functionality requested is not possible while the
panel is in fire condition.
Password must be
at least 4
characters
The new password must be at least 4 character long.
Regulated dc
supply high
The regulated DC power supply on the electronic module is
too high.
Regulated dc
supply OK
The regulated DC power supply is OK.
Reset successful
A manual fire reset from the panel was successful.
Security mode
entered
The security mode has been entered to allow access to menu
options under level - 2.
Settings saved
The changes made to settings in a form has been changed.
Settings updated
The settings made has been saved.
Sounder disabled
Alarm sounders in the system have been disabled.
Sounder enabled
The alarm sounders in the fire alarm system have been
enabled.
Split loop
allocation
cleared
The split loop fault has cleared.
Split loop
alloc'd
There is a split in the loop circuit wiring between end-1 and
end-2. Rectify the wiring fault.
System clock
adjusted
The time and date settings at the panel have been adjusted.
System clock not
set
The time and date has not been set at the panel.
Set the time and date at the panel.
System fault -
processor failure
The processor controlling the control panel has failed.
Call servicing organisation to rectify the fault.
System fault
cleared
The fault associated with the panel microprocessor has
cleared.
Too many devices
on loop
The number of devices found on the loop have exceeded the
maximum limit.
Disconnect and remove devices from loop to within the
accepted maximum range.
Unknown device
type
This device type is not recognised.
Unsaved data!!
Enter to Save or
any key
The modified data on the form has not been saved. Press
enter to save the shanges or press any key to exit the form
without saving the data.
Valid
configuration
The configuration remains valid after leaving access level 4.
Weekly fire test
due today
This is a reminder message to carryout a weekly fire test on
the system.
Zone disabled
A zone has been manually disabled.
Zone enabled
A zone has been manually enabled.
Zone test fire
The zone has been manually put into fire test state.