Any service and maintenance work on the panel or system must be carried out by a
trained maintenance engineer from the fire alarm servicing organisation.
Message displayed Description and checks
Loop allocated
The control panel has completed address allocation of each
device found on the loop.
Loop device fault
cleared
The fault associated with the loop device has cleared.
Loop device
faulty
There is a hardware fault on the device.
Replace the loop device.
Loop device lost
The device is not communicating.
Check and replace the device if necessary.
Loop device
removed
A device has been removed from the loop, for example
detector removed from its base.
Re-connect the device on the loop.
Loop device
replaced
A previously removed device has been replaced.
Loop map changed
The loop map is different to the one previously allocated.
Check the two map of loop allocations, compare them to find
the difference.
Loop map saved
The loop map has been saved.
Loop not
allocated
The loop is not allocated.
Allocate the loop.
Loop Running
The fire detection and alarm function of the loop circuit is fully
operational.
Loop Stopped
The loop has been powered down and fire/fault detection is
suspended.
Loop wiring fault
cleared
The fault associated with loop wiring has cleared.
Loop wiring
partial short
circuit
There is a partial short circuit wiring fault on the loop.
Identify the location of short circuit fault and rectify the faulty
wiring on the loop.
Loop wiring short
circuit
There is a short circuit wiring fault on the loop.
Identify the location of short circuit fault and rectify the faulty
wiring on the loop.
Mains supply
failed
The mains supply to the panel has failed.
Check the mains supply to the panel. Also check the fused
spur to the panel and the mains fuse in the panel.
Mains supply OK
The mains supply to the control panel is OK.
Maintenance visit
due
This message prompts the responsible person to call the
servicing organisation to carryout periodical maintenance work
on the system.
Master alarm 1/2
fault cleared
The fault associated with the master alarm circuit 1 or 2 has
cleared.
Master alarm 1/2
open/short
circuit
There is an open / short circuit fault on the of master alarm
sounder circuit 1 or 2.
Check the wiring and ensure the end of line resistors are fitted
on the last sounder.
New password
saved
The new password for access levels 2, 3 or 4 had been
changed and saved.
New Passwords do
not match, try
again
There is a mismatch between copy 1 and copy 2 of the new
password.
No devices found
on loop
There were no devices found on the loop circuit.
No MCPs Tested
Following a manual request for weekly fire test message at the
panel no manual call points were tested.
Panel already
reset
More than one fire reset have been performed on the panel.
There is no need to reset sucessfully reset panel.