Any service and maintenance work on the panel or system must be carried out by a
trained maintenance engineer from the fire alarm servicing organisation.
Message displayed Description and checks
Fire not reset
Initial fire is still present or there is another fire.
Fire protection
equipment fault
cleared
Open or short circuit fault associated with the fire protection
circuit has been cleared.
Fire protection
equipment OC
There is an open circuit fault associated with the fire protection
equipment circuit.
Check the fire protection equipment wiring to the panel.
Fire protection
equipment SC
fault
There is a short circuit fault associated with the fire protection
equipment circuit.
Check the fire protection equipment wiring to the panel.
Fire routing
activated
The fire routing equipment connected to the fire panel has
been manually activated.
Fire routing de-
activated
The fire routing equipment connected to the fire panel has
been manually de-activated.
Fire routing
disabled /
enabled
The output signal to fire routing equipment connected to the
panel is disabled / enabled.
Fire routing
output fault
cleared
The fault associated with the fire routing output has cleared.
Fire routing
output O/C or S/C
fault
There is an open / short circuit fault between the fire routing
equipment and the control panel. Check the wiring between
the fire routing equipment and fire panel.
Fixed ext.
equipment fault
cleared
A fault associated with the fixed extinguishing equipment (fire
protection equipment) has cleared.
Hardware fault
during start up
tba
Historic event
log erased
The historic event log was erased.
Incompatible
device
The device installed on the loop does not have an isolater
fitted.
Invalid config
data
On exiting access level 4 the panel has found discrepency in
the configuration data. Check the panel configuration.
Invalid password
The password entered is not valid. Enter correct password.
Labels cleared in
EEPROM
Left day mode
The day mode timeout has expired.
Left
Security/customer
/engineering mode
There has been an automatic return to access level 1 after a
duration of controls not being used. If required, manually re-
enter the apropriate access level.
Local input
disabled /
enabled
The local input has been disabled / enabled.
Local input fault
cleared
The short or open circuit fault on the local input lines have
cleared.
Local input O/C
or S/C fault
There is an open/short circuit fault on the local input, which
can be class change, fire input or external evacuate circuit
wiring.
Check wiring between the external equipment and fire panel.
Local input test
fire
The local fire input has been manually put into fire test state.
On completion of tests manually remove the test state from
the local fire input.