Harris ADC Device Server User’s Guide
2-14 Configuration Manager
Done Count
The number of completed events that display in the Transmission List window on the Air
Client. The valid range is from 1 to 20 events. Default is 4 events.
Thread Time
The amount of time a cart machine loads and threads a tape in a VTR prior to its
scheduled on-air time. The valid range is from 0 to 23:59:59:29 (23 hours, 59 minutes, 59
seconds, and 29 frames). Default is 2 minutes. If the Keep List Threaded box is enabled, that
setting overrides the Thread Time setting here.
Lookahead Tab
Duration Based Lookahead
Duration Based Lookahead: The Lookahead window is the area of the play list where the
automation system checks for event errors, missing media, and other possible problems.
To base the lookahead on a time duration (such as 4 hours, for example), check this box.
Default is disabled. When this option is left disabled, the Count Lookahead box to the right
is used by the automation system.
Hours: Specify a time duration, in hours, for the lookahead window to check. The
valid range is 0 to 23 hours. Default is 4 hours. This option has no effect unless the
Duration Based Lookahead box is enabled.