February 2012 25 – 407
All keys are evaluated by the NC. Certain keys are mapped to markers.
Keys that are not mapped to markers can be checked easily by verifying whether a function is called
by pressing the corresponding key or whether there is a reaction on the screen.
Checking the
potentiometers
The potentiometer setting is shown in the following PLC words:
W492 (= S override)
W494 (= F override)
8 Switch on the machine.
8 Press the EMERGENCY STOP button.
8 Activate the HR 520 (press the handwheel symbol on the HR 520).
--> The window Handwheel active appears on the screen.
8 Activate the handwheel potentiometers (see next page).
8 Call the PLC table for the words. --> See ”The TABLE function” on page 11 – 119.
8 Place the cursor on W492 or W494.
8 Select decimal display (soft key HEX<->DECIMAL).
8 Turn the potentiometer to be examined.
8 Check whether the display changes from 0 to 10000 (with nonlinear characteristic curve)
or from 0 to 100 (with linear characteristic curve).
The characteristic curve is defined in MP7620, bit 3.