4 – 44 HEIDENHAIN Service Manual iTNC 530 HSCI
Handwheel not
ready x
x = ...
A: Handwheel not attached
B: No agreement between handwheel
identification and MP7640
C: x contamination (x = axis)
D: Transfer error while receiving
E: Received BCC check sum incorrect
F: Handwheel recognized wrong identification
G: Handwheel recognized wrong BCC check
sum
H: Handwheel is signaling transmission error
I: Handwheel is signaling wrong number
of initializing parameters
J: Handwheel is signaling wrong value
of initializing parameters
K: Transfer error while sending
L: Handwheel recognized wrong axis number
of the secondary axis
M: New data received during evaluation
N: Undefined error code
Connect a handwheel.
Check the cables.
See ”Handwheel” on page 25 – 401.
Hardware error
17527
There are too many HSCI devices connected to
the control.
Disconnect some of the HSCI devices.
Inform your machine tool builder.
See ”Bus diagnosis” on page 12 – 147.
Hardware error
17528
HSCI device is not running.
The CCU did not respond within the expected
time.
CCU is defective or the firmware version is
incorrect.
Inform your machine tool builder.
See ”Bus diagnosis” on page 12 – 147.
HSCI Ethernet
connection
interrupted 14749
The Ethernet transmission is disturbed. Check the cabling.
See ”Bus diagnosis” on page 12 – 147.
HSCI Ethernet
configuration
without CC 14750
If the HSCI is configured or connected, a CC
must also be connected to the HSCI.
Check the cabling.
See ”Bus diagnosis” on page 12 – 147.
HSCI: Hardware
error 19791
An error occurred during access to the HSCI
hardware.
You can find more diagnostic information in the
diagnostics menu.
See ”Bus diagnosis” on page 12 – 147.
HSCI: Initializing
error 19792
An error occurred during initialization of the
HSCI hardware.
Y
ou can find more diagnostic information in the
diagnostics menu.
See ”Bus diagnosis” on page 12 – 147.
HSCI: IOC file is
missing 19845
Entry in OEM.SYS does not exist
IOC file does not exist
Restart the control.
Check the IOC file and OEM.SYS.
See ”Bus diagnosis” on page 12 – 147.
Error message Possible cause of error Measures for error diagnosis and/or
corrective action
Additional information and descriptions
in the manual
Additional information and descriptions
in the manual