Copyright © 2019, 2021, Hitachi, Ltd.
DKC910IHitachi Proprietary
[INST(IN)14-01-60]
Rev.1.1
INST(IN)14-01-60
Change the SVP mode to “Initial Setting”. (*3)
(SVP procedure) -- (Execution of New Installation)
(11) Dene the conguration information that you want to install now for this storage system.
(*7)
The conguration information must be dened according to the SVP guidance. Especially, you must not forget the denition
of the following information.
•
DKC Serial No.
(INST(IN)14-02-90)
(10) Before starting the following procedure, you need to enable the CE mode.
For the procedure for enabling the CE mode, see “Setting the jumper used for initial installation (CEMD)”. (MU02-200)
(12) Connect the LAN cables disconnected at (1)-4, if it is necessary.
(13) Wait till the READY LED is lit and Power Event Log (SYSTEM ON) is reported from all installed
MPs.
(14) STORAGE SYSTEM
ALARM LED lit?
(16) Power Event
Log reported from all installed
MPs?
(15) Perform operations according
to SIM/SSB indications.
(18) Perform operations according
to SIM/SSB indications.
Yes
No
(17) Wait for 40 minutes.
Yes
No
Yes
No