- 35 -
HLP-C
+
Inverters
C015 Stopping Mode
Set Range
:
0~1 Unit
:
1 Factory Setting
:
0
Two stopping modes are available for the requirements of
different equipment.
0
:
Decelerate to stop
When C093 is set as 0, DC braking is invalid. When DC braking
is invalid, the inverter will decelerate to the stopping frequency,
and then stop toutput, and the motor will have a free running
to a nal stop. When C093 is set for any non-zero value 0, the
DC braking is valid, and the inverter will rst decelerate to the
stopping frequency, and then stop nally by DC braking.
When stopping, the DC braking is usually used in high position
stopping or for position control. Be sure to notice that frequent
uses of DC braking will cause the motor overheat.
Related parameters refer to C091 and C093.
1
:
Free-running Stop
W hen the inver t er r eceives a STOP com m and , it w il l
immediately stop output and the motor will have a free running
till a stop. When the free-running stopping mode is selected for
the motor, DC braking is invalid.
C016 For/Rev Rotation
Select Set Range:0~1 Unit:1 Factory Setting:1
0:Reverse Run is forbidden.
1:Reverse Run is allowed.
This function is suitable for the motor, which cannot have
reverse rotation, to prevent workers from false operation. When
the reverse rotation is forbidden, the motor can only rotate
forward, and cannot have reverse rotation.
When the reverse rotation is forbidden, if switching between
For/Rev rotation on the panel, the panel will show Rev Run, but
the motor is actually making forward rotation with the indicator
lamp indicating For Run.
C017 STOP key Select
Set Range:0~1 Unit:1 Factory Setting:1