- 52 -
HLP-C
+
Inverters
Note:
The function of UP and DOWN is only valid when the
operation of Operator is delected for the source of the running
frequency, i.e. C013=0.
When UP is closed the inverter’s frequency will increment.
W hen DOW N is closed the inver ter’s frequency will
decrement.
When both UP and DOWNare closed at the same time the
frequency will neither increase nor decrease. It is regaded as
invalid.
When the frequency reaches the max. operation frequency it
will not increase.
When the frequency reaches the min.. frequency or its lowe
limit, it will not decrease.
It has the function of memory, including the memory for
power-off. (Setting C60=1)
When adopting the function of UP and DOWN, its up and
down speed rate is determined by the present Accel/Decel Tiem.
When keeping pressing UP or DOWN
the frequency will
increase or decrease rapidly.
The function of UP and DOWN is valid in operation. The
frequency cannot be changed during wait.
待机
F. Description of Multi-speed 1, 2 and 3 Functions
They are only valid when C024 is set to 2. Details refer to C024.
G. Description of Counter Function
t
2
t
1
Value reach
Value reset
Note:
The signal width triggered should not be lower than 2msec