- 65 -
HLP-C
+
Inverters
This parameter is valid when
C015 is set to 0. The related
parameters see C015.
C093 DC Braking Time at Stopping Set
Set Range
0.0~25.0S Unit
0.1S Factory Setting
0.0
Note: When this parameter is set to non-zero value it starts DC
brake at stopping and gives the DC brake time of the motor. DC
brake at stopping is often used for a high-level stop or position
control.
C094 Speed Search Time
Set Range
0.0~20.0S Unit
0.1S Factory Setting
2.0
This parameter is set as speed search time when the inverter
restarts by the speed search method after the external errors
or temporary power off. For the starting and stopping of some
large inertia load, because of its large inertia, if restarting the
machine after its complete stop, it will waste much time. But if
the speed search function is started, it is not necessary to wait
for the machines to come to a full stop for restart. The inverter
will search the speed from high to low with the set frequency.
After searching it it will continue to accelerate to reach the set
frequency.
C095 Speed Search Current Level
Set Range
0~200% Unit
1% Factory Setting
150
When the inverter search speed this set value sould be taken as
the level for output current. When the output current is higher
than this level the inverter will suspend searching. When the
current is restored below the current level it will then execute the
speed search again.
After starting the speed search please decrease properly the
speed search current level according to the actual condition