- 32 -
HLP-C
+
Inverters
C004 Max. Voltage
Set Range
0.1~255/510V Unit
0.1V Factory Setting
220/380
This parameter can set any intermediate voltage in the V/F
curve. If it is set improperly, it will cause motor over current or
decit torque, or even an inverter tripping.
This set value is limited by the max voltage value.
C005 Base Frequency
Set Range0.01~600.00Hz Unit0.1Hz Factory Setting50.00/60.00
C006 Intermediate voltage
Set Range
0.1~255/510V Unit
0.1V Factory Setting
*
C007 Intermediate Frequency
Set Range
0.01~600.00Hz Unit
0.01Hz Factory Setting
*
This parameter can set any intermediate frequency in the V/F
curve. If it is set improperly, it will cause motor over current or
decit torque, or even an inverter tripping.
This set value is limited by the setting of base frequency.
C008 Voltage at Lower Frequency
Set Range:0.1~* Unit:0.1V Factory Setting:*
This parameter can set the lowest starting voltage in the V/F
curve.
This setting value is limited by the voltage at the highest
operating frequency.
C009 Min. Frequency
Set Range:0.1~20.00Hz Unit:0.01Hz Factory Setting:*
This parameter sets the lowest starting frequency in the V/F
curve.
C010 Highest Running Frequency
Set Range:10.0~600.0Hz Unit:0.01Hz Factory Setting:
50.00/60.00