C064 Counter
Set Range
0~9999 Unit
1 Factory Setting
0
An external terminal of multi-function can be used as a trigger
for the counter. When the counter reaches set value C064 the
corresponding multi-function output contact will act. After
the counter is reset and returns it will start counting again. A
proximity switch or optoelectronic switch can be used for the
trigger signals.
C065 Intermediate Counter
Set Range
0~9999 Unit
1 Factory Setting
0
Intermediate Counting Value is one value of counting range.
When the counter reachesthis value the corresponding multi-
function output contact will act and output one pulse signal. It is
valid when the set value of C065 is smaller than C064.
C066 Skip Frequency 1
C067 Skip Frequency 2
C068 Skip Frequency 3
Set Range
0.00~600.00Hz Unit
0.1Hz Factory Setting
0.0
C069 Skip Frequency Range
Set Range
0.1~10.00Hz Unit
0.1Hz Factory Setting
0.5
Frequency
To avoid a mechanical resonance point three frequency hop
points are set. In case of C069=0, all hopping frequencies are
invalid. The actual hopping frequency range is two times that of
C069, as shown in the above diagram.