- 42 -
HLP-C
+
Inverters
C025 Auto PLC Operation
Set Range
:
0~3 Factory Setting
:
0
0
:
Stop after the program runs for onw week.
1
:
Cycling Running.
2
:
Stop after it runs automatically for one week
(
Stop for
intervention
)
.
3
:
Auto r un ning
(
Stop for intervention
)
and recycling
operation.
Note: This parameter set is only valid when C024 is set to 4. For
relevant parameters refer to C000, C024, C035~C049.
0
:
Stop after the program runs for onw week.
When the command of auto program running is given the
inverter start to operate with the setting of internal parameters.
It stops automatically after running for one week. Only with
another running cammand given the inverter can restart.
1
:
Cycling Running.
When the running command is given the inverter start to
operate in sequence with the section speed frequency and
running time set by each internal parameter and recyclied.
During the recycling operation, except the commands of stop,
external faults and emergency stop, all other commands will not
be accepted.
2
:
Stop after it runs automatically for one week
(
Stop for
intervention
)
Note:
(1) Whhen the command of automatic program running is given