- 86 -
HLP-C
+
Inverters
⑶
The motor can rotate reversely.
Reverse rotation is forbidden.
⑷
The motor rotatess in the opposite direction.
The output lines have been wrongly connected. Please change
any three lines of U.V.W over.
⑸
The deceloration of the motor is too slow.
①
The setting of Decel Time is too long. Decrease Decel Time.
②
Add a braking resistor.
③
Add a DC brake.
⑹
Overheat of the motor
①
Too big load. The actual torgue has exceeded the rated torgue
of the motor. It is recommended to increase the capacity of
motor.
②
The ambient temperature is too high. In a place with higher
teperaturethe motor will be burn out. Please decrease the
temperature around the motor.
③
The phase to phase withstand voltage of the motor is
insufcient.
The actions of seitches of the inverter will make the winding coil
of tehmotor produce shock wave. Normally the maximum shock
voltage will reach 3 times that of input power supply of the
inverter. Please select a motor with the phase to phase withstand
voltage against shock higher than the maximum shock voltage.
⑺
The starting of the inverter interferes other control devices
①
Lower the carrier frequency and reduce the number of actions
of the internal switches.
②
Install a noice lter on the input side of power supply of the
inverter.
③
Install a noice lter on the output side of the inverter.
④
Make correct grounding for the inverter and the motor.
⑤
Use metal tube to cover the cable to shield it.
⑥
Make separate wiring for the maon circuit wires and control
wires.