- 87 -
HLP-C
+
Inverters
When the fan starts an overcurrent stall is detected with the
inverter.
At starting the fan rotates disorderly. Please set it for DC
braking at starting.
DC braking at starting has been set. Please increase the DC
braking value.
The machine has the noise of vibration and roar
The vibration frequency of mechanical system resonates with
the carrier. Adjust the carrier to avoid the point of resonance.
The vibration frequency of mechanical system resonates with
the output frequency of the inverter.
a
Set skip function to avoid the point of resonance..
b
Put rubber vibration isolator on the base plate of motor.