- 67 -
HLP-C
+
Inverters
When the input poer supply is not stable and if the voltage is over
high the operation of the motot with the power of exceeding the
rated voltage will cause the temperature of the moto increasing,
the insulation damaged and the output torgue unstable. This auto
voltage regulation can automatically stablize the output voltage
within the rated voltage range of the motor under the condition
of unstable output power supply
When this function is set to invalid the output voltage will
uctuate.
C100 Auto Torgue Compensation
Set Range
0.1~10.0% Unit
0.S% Factory Setting
2.0
This parameter can be set for the auto output of extra voltage
when the inverter is running for higher torgue, which can
compensate for the insufcient torgue at lower frequency. The
torgue compensation should not be too big and it should be set
slowly from low to high according to the actual situation.
Insufficient compensation will result in the insufficient torgue
of the motor at low frequency. And over compensation will lead
to too bigger torgue, which will produce a shock to the machine
and even result in a trip of the inverter under serious situation.
C101 Auto Energy Saving
Set Range
0.0~20.0% Unit
1% Factory Setting
0
Torge Comp.
When it is set to 0 this function is invalid. When Auto energy
saving function is opened the inverter will run at the full voltage
during acceleration and deceleration. During the operationa
at constant speed the inverter can automatically calculate the
optimum voltage value according to the power of load to supply