Extinguishing Control Computer 8010 – 19-Inch
42 FB 798955.GB0 / 09.07
Technical Alarm Modules series 9200 / IQ8TAM (only LMST 8010 - series 3)
Required operation mode programming Î esserbus
®
zone
Connection of max. 30 technical alarm modules (with isolator) or IQ8TAM-modules per detector zone.
+
-
Detector zone X
External dry contacts (only LMST 8010 - series 3)
Required operation mode programming Î Conventional zone
The connection of external dry contacts to a detector zone input is possible. At this it must be observed that the
detector zone is terminated with a 4,7k
Ω End-of-line resistor in the last device of the zone.
4K7
+
-
Detector zone X