EasyManuals Logo

Honeywell Galaxy Dimension series User Manual

Honeywell Galaxy Dimension series
306 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #167 background imageLoading...
Page #167 background image
Galaxy Dimension Installer Manual
6-93
53 - Program Outputs (cont’d)
Key:
S = Activates when system is set ? = Activation dependant on system programming
P = Activates when system is Part Set X = Activates during Exit Time
U = Unset E = Activates during Entry Time
A = Activated in any condition L = Switches output off if linked to destination output
- = No effect T = Activates if zone resistance is less than value for tamper s/c
O= Activates when zone is omitted or greater than value for tamper o/c
Table 6-21C. Output Activations per Zone
Output Functions Timer-B Walk
Test
Zone
Omit
Warn ing Cu stom
A
Custom
B
Test Reset
RQD
Mask Valid
cd
Fail
Set
Duress Illegal
Code
Max
Tamp
Abort Unset
Zone Function 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45
01 Final UO A –S?– ––
02 Exit UO A –S?– ––
03 Intruder UO A –S?– ––
04 24 Hours UO A –S?– ––
05 Security UO A –S?– ––
06 Dual UO A –S?– ––
07 Entry UO A –S?– ––
08 Push Set UOA ––––
09 Keyswitch UOA UX–––U
10 Secure Final UOA ––––
11 Part Final UOA ––––
12 Part Entry UOA –––
13 PA UOA ––––
14 PA Silent UOA ––––
15 PA Delay UOA –––
16 PA Delay Silent UOA –––
17 Link ?U?O?? ? ? ????? ? ? ? ?
18 Spare –––A ?
19 Fire UO A –A?– ––
20 Tamper UO A –A?– ––
21 Bell Tamper UO A –A?– ––
22 Beam Pair UOA ––––––
23 Battery Low UOA –––
24 Line Fail UOA ––––––
25 AC Fail UOA ––––
26 Log UOA ––––
27 Remote Access UOA –––––
28 Video UO A –S?– ––
29 Video Exit UO A –S?– ––
30 Intruder Delay UO A –S?– ––
31 Log Delay UOA –––––
32 Set Log UOA ––––
33 Custom-A ??O?? ? ? ?????? ? ? ?
34 Custom-B ??O?? ? ???????????
35 Exitguard LLLOL L LLLLLLLL?LL
36 Mask SPE L ?
37 Urgent UO A –A?– ––
38 PA Unset UO A –U?– ––
39 Keyswitch Reset UOA ––––
40 Bell Fail A ––––
41 Intr Low UO A –S?– ––
42 Intr High UO A –S?– ––
43 PSU Fault UOA ––––
44–46 Not Used ––––
47 Vibration UO A –A?– ––
48 ATM-1 UO A –A?– ––
49 ATM-2 UO A –A?– ––
50 ATM-3 UO A –A?– ––
51 ATM-4 UO A –A?– ––
52 Alarm Extend UO A –A?– ––

Table of Contents

Other manuals for Honeywell Galaxy Dimension series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Galaxy Dimension series and is the answer not in the manual?

Honeywell Galaxy Dimension series Specifications

General IconGeneral
ModelGalaxy Dimension series
UsersUp to 250
PartitionsUp to 8
Operating Temperature-10°C to +55°C
CompatibilityHoneywell Galaxy accessories and peripherals

Related product manuals