Galaxy Dimension Installer Manual
5-9
Configuring a MAX
3
Reader into the System
NOTE: MAX
3
readers can only be configured into the Galaxy system from engineer mode.
1. Connect the MAX
3
to the Galaxy control panel as per the instructions given in Figure 5-1.
2. Access engineer mode.
3. Ensure that the Mode is enabled (option 69.1.1 = Access Control.Mode.Enabled).
4. Assign the MAX
3
reader as either On-Line or Stand-Alone using option 69.2.1 = Access
Control.MAX.MAX Address:
0 = On-Line: The MAX
3
is fully integrated with the Galaxy system and communicates via the AB line,
sharing system resources and facilities.
1 = Standalone (default): The MAX
3
operates as an entirely independent unit. The Galaxy does not
monitor the MAX
3
for alarms, tampers or power failure.
5. Press the ent key; the Galaxy panel may prompt (depending on model) for the AB line (1 – 4)) that is
to be searched; select the line and press the ent key. The Galaxy searches for the MAX
3
with the
highest address. New MAX
3
readers are addressed as 8 (standalone) by default.
6. Only if adding a new MAX
3
reader: On locating the MAX
3
address, the keypad prompts for the
OPERATING MODE of MAX
3
to be assigned: select 0 = On-Line or 1 = Standalone as required
and press the ent key.
When 0 = On-Line mode is selected, the keypad displays the current address of the MAX
3
and the
range of valid addresses. Enter the new MAX
3
address and press the ent key; the Galaxy then repro
grams the address of the MAX
3
. The keypad indicates the old and new MAX
3
addresses and the
status of the reprogramming.
NOTE: It is recommended that when adding a reader, it is addressed as the lowest available number on the
line.
7. When the reprogramming is complete the MAX
3
bleeps, the LED’s on the MAX
3
switch off and the
keypad display returns to 1 = MAX Address.
8. Exit engineer mode - engineer code + esc: the keypad displays the message 1 MOD. ADDED -
esc=CONTINUE. LED 2 on the MAX
3
reader switches on. Press the esc key; the keypad
returns to the unset banner.
If this message is not displayed, the MAX
3
reader is not communicating with the control panel
and has not been configured into the system (LED 2 does not switch on).
NOTES:
1. The MAX
3
reader will not operate until engineer mode is exited and the reader is configured into the
system.
2. All MAX
3
doors must be closed, otherwise engineer mode cannot be exited.
9. The on-line MAX
3
reader is now configured into the system.
Access Control (cont’d)