Page 164 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 13
Filter Selection
[18FLTSEL]
STDSOR
FASTSOR
Configure the desired
performance for the Output
Speed of Response Filter.
Select from: Standard SOR:
excellent speed of response to
input changes with optimal
noise performance Fast SOR:
fastest speed of response to
input changes.
Press to
enter menu
selection
Menu to
select from
list
to enter
NAMUR
[19NAMUR]
DISABLE
ENABLE
select to enable or disable the
Namur option for effect on
output signal.
Press to
enter menu
selection
Menu to
select from
list
to enter
Language
Selection
[20LNGSEL]
ENGLISH
RUSSIAN
Standard display language
selection:
Select English or Russian
option to show display in
selected language.
Press to
enter menu
selection
Menu to
select from
list
to enter
Transfer
Function
[21TXFRFN]
LINEAR
SQRT
Pressure Transfer function:
Select the pressure transfer
function for calculated output:
Linear: (output scaled linearly
per configured range) Square
Root: (output scaled as square
root conversion per configured
range - for flow
measurements).
Press to
enter menu
selection
Menu to
select from
list
to enter
Low Flow Cut
Off Mode
[22CUTFMD]
ZROFLOW
SBRKPT
DAULSLP
Low Flow Cutoff Mode:
For Square Root (Transfer
function) configurations only,
choose the operating mode to
determine the low flow cutoff
breakpoint: Dual slope:
(breakpoint determined by dual
slope calculation) User
configuration: (breakpoint
defined by user).
Zero Flow: Sets analog output
to 4mA when square root / flow
is below user defined flow
cutoff value.
Note: Sets loop output to low
saturation when the differential
pressure is below 10%Flow..
Press to
enter menu
selection
Menu to
select from
list
to enter