Revision 12 ST 700 SmartLine Pressure Transmitters User’s Manual Page 165
Low Flow Cut
Off Breakpoint
[23%FLOW]
When “User Configuration” is
selected for Low Flow Cutoff
Mode, enter the desired
breakpoint value.
Press to
enter menu
selection
to select
number.
to enter
and shift to
the next digit
to the right
SP Zero Correct
[24SPZRO]
Corrects the static
pressure to a zero
value psi for DP
transmitters only
Performs the correction of
measured static pressure value
to a value of zero psi.
Executing this selection
corrects Static Pressure Zero
based on the input static
pressure.
The live value of the static
pressure input is shown on this
display so the user can easily
see the result of the correction.
Press to
enter menu
selection
Press to
initiate action
SP Reset
Correct
[25SPRST]
Executing this selection resets
Static Pressure Zero to the
factory value of 0.
Press to
enter menu
selection
Press to
initiate action
Barometric
Standard
[26BARSTD]
Available for AP models only.
The pressure value for an
absolute pressure correction
when the pressure input is
open to the atmosphere.
Enter an atmospheric pressure
value corresponding to
barometric standard.
If the difference between the
measured atmospheric
pressure and the user-entered
barometric standard pressure
is > 1 psi (27.680672 inH2O
[4°C]) the calibration will not be
performed.
Range: 330-490 inH2O [4°C]
Default: 406.782 inH2O [4°C]
Press to
enter menu
selection
Menu to
select
number.
to enter
and shift to
the next digit
to the right