39TR80 - Installation and Operation Guide
3.6 DO-NOT-DISTURB & MAKE-UP-ROOM
Do-not-Disturb and/ Make-Up-Room functions can be enabled individually. The button on the
TR80 will be enabled only if at least one of these functions are enabled.
3.7 CLEANING MODE
It is possible to monitor if the device is currently switched to cleaning mode (Refer Cleaning
The Front Glass). This could be utilized, for example in hotel applications, to monitor if house-
keeping has already done the cleaning for a guest room.
3.8 USER INTERFACE
3. 8. 1 Backlight Brightness
Register
type
Relative
Address
Absolute
Address
DirName
Config
parameter
TypeRange
Default
value
Input330009RDnD/MuR status-enum
0: none
1: DnD
2: MuR
0
Holding201442015R/WDnD/MuR enable16enum
0: disabled
1: DnD enable
2: MuR enable
3: Dnd/Mur enable
1
Register
type
Relative
Address
Absolute
Address
DirName
Config
parameter
TypeRange
Default
value
Input10130102RCleaning mode status-enum
0: no
1: yes
0
Holding210942110R/WCleaning mode timeout107secs
10-7200
secs
60 s
Register
type
Relative
Address
Absolute
Address
DirName
Config
parameter
TypeRange
Default
value
Holding210342104R/WBacklight brightness101int0-100%100%