66 TR80 - Installation and Operation Guide
List of Lighting Configuration Parameters
210 AvailableHv
acModes
enum Bit0: "AUTO"
Bit1: "HEAT"
Bit2: "COOL"
Bit3: "FAN"
Bit4: "OFF"
Bit5: "HTG1"
Bit6: "HTG2"
Bit7: "CLG1"
Bit8: "CLG2"
15 Default : Auto/Heat/Cool/Fan
Config
parameter
number
Name
Type/
Unit
Range
(min-Max)
Default Notes
Config
parameter
number
Name
Type/
Unit
Range
(min-Max)
Defau
lt
Notes
300 Light Group Count - 0…4 2
301 Light adjust step size enum 0 : 1%
1 : 2%
2 : 5%
3: 10%
4: 20%
3
302 Light Group 1 type enum 0: on-off / 1: dimmable 1
303 Light Group 1 min
level
% 0…100% 1%
304 Light Group 1 max
level
% 0…100% 100%
305 Light Group 1 Max
Scene No
int 0-16 4 0 = scene selection disabled
306 Light Group 2 type enum 0: on-off / 1: dimmable 1
307 Light Group 2 min
level
% 0…100% 1%
308 Light Group 2 max
level
% 0…100% 100%
309 Light Group 2 Max
Scene No
int 0-16 4 0 = scene selection disabled
310 Light Group 3 type enum 0: on-off / 1: dimmable 1
311 Light Group 3 min
level
% 0…100% 1%