TR80 - Installation and Operation Guide58
0111 (224) : mg/m3
1000 (256) : ug/m3
1001 (288) : ppm
1010 (320) : ppb
Bits 11..9: air quality icons
000 (0): none
001 (512): CO2
010 (1024): TVOC
011 (1536): PM2.5
100 (2048): PM10
Bit 13..12: Value alignment
00 (0) : right align;
01 (4096) : center
10 (8192): left align
3. 13. 4 Display Values Configuration
If no updates are received from the master controller for any value for the time defined in
'Display Values Receive Timeout', that value is considered stale and dropped from the list
to be displayed, until a fresh value is received again. This function can be disabled by set-
ting the parameter to 0.
‘Home Display Parameter’ is the display value that the screen returns to when no buttons
are touched for a while. It can be selected as follows. If this is set for ‘auto-scroll’ the screen
will automatically scroll between available values every few seconds.
0: auto-scroll
1: Room Temperature
2: Set Temperature
3: Room Humidity
4: Room Air Quality
5: Room CO
2
6: Pressure
7: Air flow volume
8: Outdoor Temperature
Register
type
Relative
Address
Absolute
Address
DirName
Config
Parameter
UnitRange
Default
value
Holding260042601R/WHome display parameter600enumsee below1
Holding260142602R/W
Display values receive
timeout
601min0-60 mins5
Holding260242603R/W
TVOC unit
(unit to display for
register 1602)
602enum
0: ug/m3
1: mg/m3
2: ppm
3. ppb
0