TR80 - Installation and Operation Guide69
List of Occupancy configuration Parameters
Config
parameter
number
Name
Type/
Unit
Range
(min-Max)
DefaultNotes
500Occupancy
Source
enum0: Modbus only
1: Button only
2: Modbus & override from
button
00: Modbus only
(button disabled)
1: Button only (simple
mode, no override,
only occupied/
unoccupied switching
on WM)
2: Modbus with
override from button
(advanced mode)
501Holiday default
days
days1-457 days
502Bypass default
minutes
minutes10-1440180 mins
503Bypass time
adjust step
minutes
enum0: 10 mins
1: 20 mins
2: 30 mins
3: 60 mins
2
504Allowed
overrides from
OFF
bitmapbit0: unused
bit1: unused
bit2: Allow override to
OCCUPIED
bit3: Allow override to OFF
bit4: Allow override to
HOLIDAY
bit5: Allow override to
UNOCC
bit6: Allow override to
STANDBY
bit7: Allow override to
BYPASS
0These registers used
to define which
override are available
in which occupancy
mode.
Short-press is
automatically
assigned to one of the
below, in order of
preference:
- OCC
- UNOCC
- BYPASS
505Allowed
overrides from
UNOCC
bitmap144: HOL &
BYPASS
506Allowed
overrides from
STANDBY
bitmap148: OCC, HOL
& BYPS
507Allowed
overrides from
OCC
bitmap176: UNOCC,
HOL & BYPS