47TR80 - Installation and Operation Guide
•Bits 0..2:
•000 (0): heat & cool not available (grey ring)
• 001 (1): Cooling mode (blue ring)
•010 (2): Heating mode (orange ring)
•011 (3): Heating+cooling (purple ring)
•100 (4): Fan-only (green ring)
•101 (5): Alarm (red ring)
•Bits 9..8 (only if orange)
•00 (0): All heat outputs off (steady ring)
•01 (256): Heat 1 Output on (slow breath)
•10 (512): Heat 2 Output on (medium breath)
•11 (769): All heat outputs on (fast breath)
•Bits 11..10 (only if blue)
•00 (0): All cool outputs off (steady ring)
•01 (1024): Cool 1 Output on (slow breath)
•10 (2048): Cool 2 Output on (medium breath)
•11 (3096): All cool outputs on (fast breath)
•Bit 12 (4096): Fan output on (medium breath - only if green)
3.10 OCCUPANCY
Occupancy mode selection on the TR80 can go beyond simple occupied/unoccupied states.
Following occupancy states are possible:
•Off
•Unoccupied (displayed as AWAY on device)
•Standby
•Occupied (dispayed as COMFORT on device)
•Standby
•Holiday
3. 10. 1 Occupancy source
TR80 allows different options for occupancy selection:
1.Button only: In this simple operation, the wall module is the only source for occupancy. User
simply uses the occupancy button to switch between occupied/unoccupied modes manu-
ally No other modes are available.