TR80 - Installation and Operation Guide65
List of HVAC Configuration Parameters
Config
parameter
number
Name
Type/
Unit
Range
(min-Max)
DefaultNotes
200Setpoint
style
enum0: absolute
1: relative
0: absolute
201Setpoint
minimum
signed int
(°C / K)
absolute mode: -50….+150
relative mode: -15…….0
absolute: 10 °C
relative: -5 K
202Setpoint
maximum
signed int
(°C / K)
absolute mode: -50….+150
relative mode: 0…….15
absolute: 30 °C
relative: +5 K
203Default
Setpoint
°C10….30 °C22 °C
204Fan typeenum0: no fan
1: Single speed fan
2: Two-speed fan
3: 3-speed fan
4: EC fan
3
205EC Fan
speed
adjust step
size
enum0: 1%
1 : 2%
2 : 5%
3: 10%
4: 20%
3: 10%For EC fans only
206Fan speed
low-limit
% or int0-100 % for EC fans,
0-3 for others
0
207Fan speed
high limit
% or int0-100 %
0-3 for others
100
208Fan UI
attributes
bitmapBit 0: Fan override (0: No
ovrd, 1: Allow ovrd)
Bit 1: Display of 1-stage
fan (0: 1 bar, 1: 3 bars)
Bit 2-16: reserved
1If fan override not allowed,
disable fan button but keep
speed indication & AUTO symbol
209HvacMode
SelectionTy
pe
enum0: disabled
1: simple
2: advanced
0