Configuration
38 UDC3300 Expanded Model: DC330E User Manual 5/00
Function
Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
XMITTER2
Transmitter
Characterization
B TC S TC
E TC H T TC H
E TC L T TC L
J TC H W TC H
J TC L W TC L
K TC H 100 PT
K TC L 100 LO
NNM H 200 PT
NNM L 500 PT
NM90 H RAD RH
NM90 L RAD RI
NIC TC LINEAR
R TC SQROOT
ANALYT
LINEAR
ANALYTIC
Analytic Selections
XMITTER2 must be set to
ANALYT for this prompt to
appear
NONE
PH
ORP Mv (Millivolts)
CONDms (Milli Siemens)
CONDus (Micro Siemens)
RSTVM^ (Megaohms)
TDS PPm (Parts per Million)
TDS PPb (Parts per Billion)
CONCPt (Parts per Thousand)
DO PPm (Parts per Million)
DO PPb (Parts per Billion)
NONE
IN2 HI
Input 2 High Range Value
(Linear Inputs only)
–999. to 9999. floating
(in engineering units)
1000
IN2 LO
Input 2 Low Range Value
(Linear Inputs only)
–999. to 9999. floating
(in engineering units)
0
RATIO 2
Input 2 Ratio –20.00 to 20.00 1.000
BIAS IN2
Input 2 Bias –999. to 9999.
(in engineering units)
0
FILTER 2
Input 2 Filter 0 to 120 seconds 1
BURNOUT2
Burnout Protection NONE DOWN
UP NO_FS
NONE
EMISSIV2
Emissivity 0.01 to 1.00 0.00