Configuration
34 UDC3300 Expanded Model: DC330E User Manual 5/00
Function
Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
TOTALIZE
Totalization Function DISABL
INPUT1
IN AL1
IN AL2
DISABL
ΣXXXXXXX
Current Scale Factor
(upper display)
Actual Current Totalized
Value (lower display)
Σ*En
Where:
n = Totalizer Scale Factor
Value
- -
TOT SCAL
Totalizer Scale Factor *E0
*E1
*E2
*E3
*E4
*E5
*E6
E0
TOT SEC
Totalizer Reset Lock UNLOCK
LOCK
UNLOCK
Σ RSET ?
Totalizer Reset NO
YES
NO
TOT RATE
Totalizer Rate of
Integration
SECOND(once per second)
MINUTE (once per minute)
HOUR (once per hour)
DAY (once per day)
ML/DAY (millions per day)
SECOND
3.8 Output Algorithm Parameters Set Up Group
Table 3-7 Output Algorithm Group Function Prompts
Function
Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
OUT ALG
Loop 1 Output Algorithm TIME Time Simplex
CURRNT Current Simplex
POSITN Position Proportional
TIME D Time Duplex
CUR D Current Duplex
CUR TI Current /Time Duplex
TI CUR Time/Current Duplex
CURRNT
4–20 RNG
Current Duplex Range 100PCT
50 PCT
100PCT