Configuration
5/00 UDC3300 Expanded Model: DC330E User Manual 29
Function
Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
SEG 3, 5, 7, 9 &
11 RAMP
SEG 3, 5, 7, 9, &
11 RATE
SEG 4, 6, 8, 10 &
12 SP
SEG 4, 6, 8, 10 &
12 TIME
Same as above Selections are same as above. ––
3.6 Accutune Set Up Group
Table 3-5 Accutune Group Function Prompts
Function
Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
FUZZY
Fuzzy Overshoot
Suppression
DISABL
ENABLE
ENABL2
ENAB12
DISABL
ACCUTUNE
Accutune DISABL
TUNE (Demand Tuning)
SP (SP Tuning)
TUN+PV
SP+PV
DISABL
ACCUTUN2
Accutune Loop 2 DISABL
TUNE (Demand Tuning)
SP (SP Tuning)
TUN+PV
SP+PV
DISABL
SP CHANG
Setpoint Change Value
Loop 1
5 to 15% Input Span 10
KPG
Process Gain Loop 1 0.10 to 10.00 1.00
SP CHAN2
Setpoint Change Value
Loop 2
5 to 15% Input Span 10
KPG 2
Process Gain Loop 2 0.10 to 10.00 1.00
CRITERIA
Tuning Criteria Loop 1 NORMAL
FAST
FAST