Configuration
30 UDC3300 Expanded Model: DC330E User Manual 5/00
Function
Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
CRITERA2
Tuning Criteria Loop 2 NORMAL
FAST
FAST
AT ERROR
OR
AT ERR2
Accutune Error Codes Read Only
RUNING (Accutune process
in operation)
NONE
OUTLIM
IDFAIL
ABORT
LOW PV
- -
3.7 Algorithm Data Set Up Group
Table 3-6 Algorithm Group Function Prompts
Function
Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
CONT ALG
Control Algorithm ON-OFF
PID A
PID B
PD+MR
3PSTEP
PID A
PIDLOOPS
PID Loop Selection 1 LOOP
2LOOPS
CASCAD
1 or 2
CONT2ALG
Control 2 Algorithm PID A
PID B
PD+MR
PID A
OUT OVRD
Output Override Select DISABL
HI SEL
LO SEL
DISABL
TIMER
Timer Enable/Disable ENABLE
DISABL
DISABL
PERIOD*
Timeout Period 00:00 to 99:59 00:01
START*
Start Initiation KEY (Run/Hold key)
ALARM2
KEY
L DISP*
*
prompts appear
only when Timer is
enabled
Lower Display Selection TI REM (time remaining)
E time (elapsed time)
TI REM