Setpoint Rate/Ramp/Soak Program Operation
5/00 UDC3300 Expanded Model: DC330E User Manual 87
Contents Definition
Hot Start
This function determines whether LSP1 or PV is used as the setpoint when
the program is initially changed from HOLD to RUN. The selections are:
• DISABL = present LSP1 is default setpoint
• ENABL = present PV value is used as beginning setpoint value for the
ramp segment
Reset Program
to Beginning
When enabled, this selection allows you to reset the program to the
beginning or rerun it from the keyboard.