HEATING SYSTEM CONTROL
54 4 213 563 / 03
NEW from to °C
00:00 05:30 45
05:30 08:00 50
08:00 15:30 45
15:30 22:00 50
22:00 00:00 45
I create my own day program and adapt
the switching cycles individually to my
requirements. I use the switching cycles
of the “Early & late” day program as a
template.
5.11.6 Legionella function
Legionella are bacteria that can cause Legionnaire’s di-
sease. The optimum conditions for these bacteria to exist
are hot water that is kept between 25 and 50 °C for long
periods. Legionella are killed o󰀨 when the full content of
the water tank is heated through to 60 °C. The TopTronic
®
E control module includes a separate hot water day pro-
gram (all day legio) that can be activated once a week in
the week program.
The legionella function can be activated in
the Main menu ( ) > Programs
(5.12.6 page
63) by allocating the “all day legio” day pro
-
gram in the week program.