Specifications
Environmental specifications
Specifications Value
Temperature range*
—
Operating 10°C to 35°C (50°F to 95°F)
Nonoperating -30°C to 60°C (-22°F to 140°F)
Relative humidity (noncondensing)
—
Operating
8% to 90% - Relative humidity (Rh), 28°C (824°F) maximum wet bulb
temperature, non-condensing
Nonoperating
5 to 95% relative humidity (Rh), 387°C (1017°F ) maximum wet bulb
temperature, non-condensing
Altitude
—
Operating 3050 m (10000 ft). This value may be limited by the type and number of
options installed. Maximum allowable altitude change rate is 457 m/min (1500
ft/min).
Non-operating 9144 m (30000 ft). Maximum allowable altitude change rate is 457 m/min
(1500 ft/min).
Standard operating support
10° to 35°C (50° to 95°F) at sea level with an altitude derating of
10°C per every 305 m (18°F per every 1000 ft) above
sea level to a maximum of 3050 m (10000 ft), no direct sustained sunlight. Maximum rate of change is 20°C/hr (36°F/hr).
The upper limit and rate of change may be limited by the type and number of options installed.
System performance during standard operating support may be reduced if operating with a fan fault or above 30°C
(86°F).
Extended ambient operating support
For approved hardware configurations, the supported system inlet range is extended to be: 5° to 10°C (41° to 50°F) and
35° to 40°C (95° to 104°F) at sea level with an altitude derating of
10°C per every 175 m (18°F per every 574 ft) above
900 m (2953 ft) to a maximum of 3050 m (10000 ft). The approved hardware configurations for this system are listed at
the Hewlett Packard Enterprise website.
40°C to 45°C (104°F to 113°F) at sea level with an altitude derating of 10°C per every 125 m (18°F per every 410 ft)
above 900 m (2953 ft) to a maximum of 3050 m (10000 ft). The approved hardware configurations for this system are
listed on the Hewlett Packard Enterprise website.
System performance may be reduced if operating in the extended ambient operating range or with a fan fault.
Specifications